HVAC Sensor Range & Output Selector
Pick the application, enter the band you actually need to measure, and get a standard measuring range, the sensor type that suits it and the output signal to specify. Covers temperature, differential pressure, humidity and CO2.
The three rules behind the recommendation
- The range must cover the whole operating band. A sensor that clips at the edge of normal operation is worse than no sensor, because the controller cannot tell “at the limit” from “past the limit”.
- It should not be much wider than the band. Resolution, accuracy and repeatability are all quoted against full span, so an oversized range multiplies every error by the same factor.
- Both ends of the band want some headroom. Enough for start-up and pull-down excursions, but not so much that the useful part of the signal collapses into a narrow slice of the scale.
In practice this means choosing the smallest standard range that still contains your band — which is exactly what the tool does. If your band fills more than about 90 % of the range, step up one size; if it fills less than 20 %, step down.
Typical ranges by application
| Application | Typical band | Standard range | Usual signal |
|---|---|---|---|
| Chilled / hot water pipe | 5–60 °C | 0–100 °C | 4–20 mA |
| Domestic hot water | 45–70 °C | 0–100 °C | 4–20 mA |
| Steam / high-temp water | 100–180 °C | 0–200 °C | 4–20 mA |
| Supply / return air in duct | 12–38 °C | −20–80 °C | NTC 10 kΩ |
| Room air | 18–28 °C | 0–50 °C | NTC 10 kΩ |
| Outdoor air | −15–42 °C | −50–50 °C | NTC 10 kΩ |
| Duct static pressure | 50–800 Pa | 0–1000 Pa | 0–10 V |
| Water differential pressure | 20–150 kPa | 0–200 kPa | 4–20 mA |
| Relative humidity | 25–90 %RH | 0–100 %RH | 0–10 V |
| CO2 (DCV) | 400–1500 ppm | 0–2000 ppm | 0–10 V |
Bands are the values seen on ordinary commercial jobs; ranges are the sizes sensor makers normally stock. Treat them as a starting point, then confirm against the project's design conditions.
Element choice in one line each
- NTC 10 kΩ — cheapest and the default for room and duct air; non-linear, so it needs the controller's matching curve.
- PT100 / PT1000 RTD — linear, stable and interchangeable; the choice for water, steam and anything that has to stay accurate for years.
- 4–20 mA transmitter — converts any element into a signal that survives long cable runs; needs a loop supply and two wires per point.
- 0–10 V transmitter — simpler wiring and fine inside a plant room, but keep the run short and the screening good.
- Passive elements on a bus — where the controller already speaks a fieldbus, a passive element on a bus module is usually cheaper per point than individual transmitters.