1. Why thermostat–valve mismatches keep happening on site
Walk onto almost any fan coil unit commissioning job and you will find the same scene: a thermostat from one supplier, a valve actuator from another, and a terminal block in between that nobody fully documented. The thermostat works. The actuator works. Put them together and the valve either never opens, creeps open when it should be closed, or cycles itself to death. The root cause in most cases is a mismatch between the output type of the thermostat and the input type of the actuator — two sides of the same control loop that are rarely ordered as a matched pair.
This guide is the reference we give our own OEM customers. It covers the four output families you will meet on FCU and heating thermostats, the five input types you will meet on valve and damper actuators, a compatibility matrix you can keep on the wall, and the electrical traps (VA sizing, leakage current, mixed voltages) that cause most field failures.
2. The output families found on HVAC thermostats
2.1 Voltage-free relay outputs (dry contacts)
The classic output. A mechanical or solid-state relay closes a contact that carries whatever voltage the field wiring supplies — typically 24 VAC, 230 VAC, or a DC supply. On the drawing it appears as SPST (single heating or cooling stage), SPDT (changeover, used for heating/cooling selection or 3-speed fan switching), or multi-relay blocks for fan speeds.
Check three ratings before you trust a relay output: contact current (commonly 2–6 A resistive), maximum switching voltage, and whether the rating is for resistive or inductive loads. A relay rated 3 A resistive will not enjoy switching a 230 V motor inrush for years.
2.2 Triac and electronic driver outputs
Electronic thermostats often switch fan speeds or small loads with a Triac instead of a relay: silent, no contact wear, cheap. Two properties matter for matching. First, a Triac is polarised to AC and leaks a small current (typically under 1–2 mA) even when “off”. Second, many Triac outputs are referenced to the thermostat’s own supply phase, so they are not truly voltage-free. They are excellent for driving 24 V fan relays and small motorized actuators; they are a known trap for thermal actuators and LED-indicating circuits, as we will see in section 5.
2.3 Floating (tri-state, 3-point) outputs
A floating output is two interlocked relay contacts — “drive open” and “drive close” — never closed together. The controller pulses one contact for a fixed time, and the actuator’s internal motor moves in that direction. The controller does not know the position unless it counts run time itself. On terminals you will see it as three wires: common, open, close (sometimes labelled Y1/Y2 or ↑/↓).

2.4 Analog outputs: 0–10 V and 2–10 V
An analog output commands proportional position directly: 0 V = closed (or minimum), 10 V = open. The 2–10 V variant exists because 0 V cannot be distinguished from a broken wire — with 2–10 V, zero signal is out of range and the controller or actuator can raise a fault or drive to its fail-safe position. Most thermostats labelled “0–10 V” are in practice configurable for either range.
2.5 Digital bus outputs (Modbus RTU, BACnet MS/TP)
Increasingly the “output” is not a signal at all but a data point on an RS-485 bus. Setpoint, mode, fan speed and valve position travel as registers. The valve actuator may still be conventional (the thermostat converts the bus command to its own 0–10 V or relay output), or the actuator itself is bus-native. For a deeper treatment see our guides on Modbus FCU thermostats and BACnet MS/TP thermostat selection.
3. The input types on valve and damper actuators
3.1 On/off motorized actuators
Two or three wires, one direction: energise and the actuator drives to the open position; de-energise and it either stays (non-spring, power-off in place) or returns (spring return). Travel time is typically 15–150 seconds for valve actuators, longer for large dampers. Internally, limit switches cut the motor at the ends of travel.
3.2 Thermal actuators
A resistive heater (typically 24 V, around 2–3 W) warms a wax or fluid element that pushes a pin — the mechanism behind most compact zone valve actuators on fan coils. They are silent, cheap and slowly stroking: full lift in roughly 2–6 minutes, closure in a similar or slightly longer time. They draw a continuous few watts whenever energised, and they only know two positions: energised = open, de-energised = closed.
3.3 Floating-point actuators (3-wire)
Internally a reversible motor: apply power between common and “open”, the motor runs open; between common and “close”, it runs closed. A built-in feedback potentiometer is common (a fourth wire, 0/2–10 V position signal) even when the control input itself is floating. Because the actuator runs only while pulsed, the controller can park it anywhere and hold with zero power.

3.4 Modulating actuators (0–10 V / 2–10 V input, 2–10 V feedback)
The actuator contains its own positioning electronics: it compares the commanded signal with its measured stem or shaft position and drives until they match. Input is 0–10 V or 2–10 V (sometimes 4–20 mA with a 500 Ω shunt); feedback is almost always 2–10 V so that a true 0 V readback is distinguishable from a fault.
3.5 Bus-native actuators
Modbus RTU or BACnet MS/TP inside the actuator housing. Position commands and feedback are registers; power is the only pair of wires that matters electrically. Increasingly seen on AHU dampers and larger valves, still rare on FCU zone valves.
4. The compatibility matrix
| Thermostat output ↓ / Actuator input → | On/off (2-wire) | Thermal (24 V) | Floating (3-wire) | Modulating (0–10 V) | Bus (RS-485) |
|---|---|---|---|---|---|
| Relay, SPST | Direct match | Direct match (verify 24 V and continuous wattage) | Half control only — one direction; use only where fail-to-close is acceptable | No (relay is binary; an adapter module is required) | No |
| Relay, SPDT (changeover) | Direct match | Direct match | Match — the standard pairing for floating control | No (adapter required) | No |
| Triac / driver outputs | Match with care — check voltage reference and leakage | Trap — leakage can hold a thermal actuator partially open (see 5.3) | Possible if two Triacs are interlocked and share the reference; verify with the manufacturer | No | No |
| Floating output | Use only the “open” contact; the second contact stays spare | Use only the “open” contact | Direct match | No | No |
| 0–10 V / 2–10 V output | No (0 V is not a valid “closed” command for a motorized actuator) | No | No | Direct match | No |
| Modbus / BACnet thermostat | Yes — via the thermostat’s own relay output | Yes — via relay output | Yes — via its floating outputs | Yes — via its analog output | Native match if both devices share the bus protocol |
The takeaway: relays pair with on/off and thermal inputs, SPDT pairs with floating, analog pairs with modulating. Everything else needs an interface module — which is not a failure, just a part you must order.
5. Voltage, VA sizing and the leakage-current trap
5.1 Match coil voltages and keep SELV separated
The single most damaging wiring error we see in OEM support is a 24 V thermostat contact switched into a 230 V actuator circuit “because the contact is voltage-free anyway”. Electrically it can work; in practice it puts low and mains voltage into one terminal box, violates the isolation concept of every SELV thermostat, and fails inspection. Decide per loop: either the whole thermostat–actuator pair runs 24 V, or the thermostat is explicitly rated for mains switching on that output.
5.2 Size the transformer for the worst case
Sum the continuous VA of every 24 V device on the transformer: thermostat (typically 3–8 VA), thermal actuators (2–3 W each, and they are energised for most of the season), motorized actuator running current, plus any relays and sensors. Then apply a 25–30% margin for inrush and aging. An undersized transformer shows up as thermostats that reboot when several valves stroke at once — the classic Monday-morning start-up failure.
5.3 Triac leakage versus thermal actuators
A thermal actuator needs only a few watts to stay open, so even 1–2 mA of Triac leakage through its high-resistance coil can keep the element warm enough to hold the valve cracked open — the valve that “never fully closes”. Fixes, in order of preference: choose a thermostat with true relay outputs for thermal actuators; fit the bleed/snubber network recommended by the thermostat manufacturer; or switch to a motorized (inductive) actuator that tolerates the leakage. The same leakage also makes LED pilot lamps glow dimly in the dark — same physics, less harm.
5.4 One 0–10 V output, several actuators?
Parallel actuators divide the source’s drive capability by their input impedances and all move identically — acceptable for two or three identical dampers fed from one controller with adequate drive current, never a way to give two valves “independent” positions. Check the source’s maximum load (often quoted as a minimum load resistance, e.g. 500 Ω) before paralleling.
6. Interlocks and end switches you should not skip
The thermostat–valve pair rarely lives alone. Three interlocks belong in the specification:
- Fan–valve interlock: a valve end switch (SPDT, switches at ~5% travel) proves water flow before the fan is allowed to run — preventing a coil full of still air from freezing or cooking depending on season. Most quality zone actuators offer an end switch or auxiliary switch as an option; order it, wire it, and enable the interlock in the thermostat.
- Pump/booster run signal: in systems with a shared loop pump, a “any valve demanding” signal (parallel end switches into one relay) prevents the pump from running against a closed field.
- Damper aux switches: on fire-and-smoke duties the aux switch proves damper position back to the fire system — see our guide on spring return damper actuators for where fail-safe position is mandated.
7. Field commissioning checklist
- Confirm thermostat output type (relay/SPDT/floating/0–10 V) from the datasheet — not from the terminal label alone.
- Confirm actuator input type, coil voltage and (for thermal) continuous wattage.
- Confirm the compatibility from the matrix above; order interface modules now, not on site.
- Measure transformer loading: sum of VA × 1.3 < transformer rating.
- For Triac outputs driving thermal actuators: measure leakage current, fit snubber if the valve creeps.
- Stroke-test the pair: command 0%, 50%, 100% and time the travel; compare with the actuator datasheet.
- Verify feedback (2–10 V or potentiometer) tracks command within ~5%.
- Wire and prove the fan–valve end-switch interlock.
- Label every terminal box with the loop voltage (24 V / 230 V).
- Record thermostat model, actuator model and settings in the handover sheet.
8. Frequently asked questions
Can I drive a floating actuator from a thermostat with only SPST relay outputs?
Only in one direction — the single contact can command “open” and de-energising stops the actuator where it is (or, on some actuators, drives it closed on loss of power). You lose the ability to command closing while powered. For true floating control you need a changeover (SPDT) output or a second relay.
Why does my 0–10 V thermostat not fully close a valve labelled “0–10 V”?
Many modulating actuators treat 0 V as “out of range” and either drive to fail-safe or hold last position. Check whether the actuator input is 0–10 V or 2–10 V, and whether the thermostat’s minimum output is truly 0.0 V or has a live-zero offset. Setting both to the same range usually solves it in minutes.
Is a thermal actuator “modulating” because it moves slowly?
No. Slow is not proportional. A thermal actuator is binary — energised or not — with a slow, temperature-dependent stroke. Proportional control needs a modulating input (0–10 V) and internal position feedback.
How many thermal actuators can one 24 VA transformer supply?
At roughly 2–3 W (≈3 VA) each plus the thermostat, four to six actuators is a comfortable ceiling once you keep the 25–30% margin — but always recalculate with the actual nameplate figures and include fan relays and sensors on the same winding.
Can a BACnet thermostat drive a plain 230 V on/off valve?
Yes, if the thermostat’s relay output is rated for 230 V switching. Most bus thermostats still expose conventional relay and analog outputs precisely so they can drive “dumb” actuators; the bus is then only between thermostat and BMS.
What is the cleanest way to retrofit proportional control into a relay-wired FCU?
Replace the on/off actuator with a 0–10 V modulating actuator and the thermostat with one that has an analog output — or add a small relay-to-analog interface module if the thermostat is otherwise healthy. Rewiring is limited to the actuator drop; the loop becomes “0–10 V end to end”, which is the configuration we recommend for new OEM projects (see our 0–10 V and 4–20 mA signal guide).
Match your thermostat and valve families with DANRENS
DANRENS is an OEM/ODM manufacturer of HVAC control products from our own facility in Quanzhou, China: FCU thermostats, motorized valves, damper actuators and HVAC sensors, with 100% function testing before shipment. Tell us your thermostat output and valve duty and our engineers will confirm the matched pair within 24 hours: contact the DANRENS engineering team.
Related reading: 0-10 V and 4-20 mA Signal Guide · FCU Thermostat Wiring Field Guide · Electric Valve vs Solenoid Valve.
Need Help Specifying or Sourcing?
Tell us your system type, required quantity and target market — our engineers reply within 24 hours with matched models and a quotation.
Back to Blog