Indoor air quality is usually debated as an equipment question when it is really a control question. The complaints — stuffy meeting rooms, afternoon headaches, dry eyes, the sense that “the air conditioning is broken” — arrive from occupants long before any plant fault shows up on a screen. In most buildings the plant is fine and the ventilation is simply not following the occupancy. This guide covers what IAQ actually consists of, why ventilation is the first lever, how demand-controlled ventilation works, and what to specify so the numbers become measurable instead of assumed.
What indoor air quality actually covers
IAQ is not one measurement. Four families of contaminant drive almost every complaint, and they need different responses.
- Carbon dioxide and other occupant-generated gases. CO2 is not toxic at the concentrations found indoors. Its value is as a proxy: it rises predictably with the number of people in a space relative to the fresh-air rate, which makes it the most useful single indicator of whether ventilation is keeping up.
- Particulates. PM2.5 and PM10 — outdoor pollution drawn in with the fresh air, plus fibres and dust generated indoors.
- Humidity. Both extremes cause problems. Dry air produces eye and throat irritation and static; persistently damp air supports microbial growth in ducts, coils and ceiling voids.
- Volatile organic compounds and combustion gases. Off-gassing from finishes and furniture, plus any combustion appliance, which is why carbon monoxide detection is a safety matter rather than a comfort one.
The practical consequence is that a space can be perfectly comfortable in temperature terms and still be badly ventilated. Temperature control and air quality control are different loops that share a room.
Why ventilation is the first lever
Filtration removes particles; ventilation removes everything else. Fresh air dilutes occupant-generated gases and odours that no filter can catch, which is why ventilation rate per person sits at the centre of every IAQ discussion. The reference points most projects work to are ASHRAE Standard 62.1 for commercial buildings, ASHRAE Standard 62.2 for residential, and EN 13779 for non-residential ventilation in Europe. Local codes take precedence, and the outdoor-air rate they set is a minimum, not a target.
The tension is obvious: outdoor air has to be heated, cooled, dehumidified and filtered before it reaches the space, so more fresh air means more load. A design that supplies full outdoor-air rate continuously — the traditional constant-volume approach — is therefore correct on paper and expensive in practice, because buildings are rarely at design occupancy. That gap is exactly what demand-controlled ventilation closes.
Demand-controlled ventilation: measure instead of assume
Demand-controlled ventilation (DCV) replaces a fixed outdoor-air rate with a rate that follows the space. The control loop is straightforward: measure an indicator of occupancy or air staleness, then modulate the outdoor-air damper, the return damper, the fan speed or a combination of the three until the indicator sits at its target.
CO2 is the indicator usually chosen, for three reasons. People exhale it, so its concentration tracks occupancy per unit of ventilation. It is cheap to measure accurately with a mature sensing technology. And it responds to the thing you are actually trying to control — whether the fresh-air rate is adequate.
A common design target is to hold occupied spaces below roughly 800–1,000 ppm CO2, with a higher unoccupied allowance so the loop does not chase an empty room. Treat that figure as an engineering starting point and confirm it against the local code and the owner’s brief; the exact number is a project decision. What matters more is the strategy: a target with a dead band and a defined unoccupied setpoint, rather than a controller oscillating on a single threshold.
The energy argument follows from the load. Ventilation air is one of the largest single loads in a modern commercial building, and DCV reduces it whenever occupancy is below design. The saving comes from the ventilation load, not from the terminal units, which is why DCV economics are strongest in spaces with highly variable occupancy: meeting rooms, classrooms, auditoria, restaurants and retail floors.
Choosing a CO2 transmitter
The sensing method matters more than the feature list. Non-dispersive infrared (NDIR) is the standard technique for CO2 measurement and the one to look for on a specification sheet.
- Duct or wall mount. A duct transmitter reading the return air gives a zone-average figure, which is usually the right input for ventilation control and needs one device instead of many. A wall-mount unit measures the space locally, which suits control of a single room or where duct access is poor.
- Range. A 0–2,000 ppm span covers occupied spaces comfortably; wider ranges usually trade resolution for headroom you will not use.
- Output and scaling. 0–10 V, 4–20 mA or Modbus RTU — it has to match the controller input, and the scaling has to be written on the drawing. A 0–2,000 ppm transmitter scaled as 0–1,000 produces a loop that looks stable and ventilates half as much as intended.
- Self-calibration. NDIR sensors drift slowly. Automatic baseline correction uses the fact that a building regularly empties and returns to near-outdoor CO2 levels overnight. It works well in offices and schools; it is unreliable in a space that is genuinely occupied around the clock, which is a site question rather than a product one.
- Humidity alongside. A CO2 reading says nothing about moisture. If the brief includes occupant comfort or microbial control, pair the CO2 measurement with a temperature and humidity transmitter on the same bus.
DANRENS builds the DSAE-2101 duct CO2 sensor for exactly this role, and the wider sensor range covers temperature, humidity and CO2 transmitters on the same signalling convention, so a ventilation loop and a comfort loop can share a controller and a wiring standard.
Filtration, humidity and pressure balance
Ventilation and filtration are complements, not alternatives. Once the outdoor-air rate is right, three further details decide whether the space feels right.
- Filter selection. ISO 16890 classifies filters by their efficiency against PM1, PM2.5 and PM10, which is more directly useful than the older EN 779 classes it replaced. MERV ratings remain common in North America and cross-reference approximately.
- Loading and pressure drop. A filter that has loaded to twice its clean pressure drop is both an energy penalty and a ventilation-rate problem, because the fan moves less air. Differential pressure monitoring turns a calendar-based guess into a measured trigger.
- Humidity. A band of roughly 40–60 % RH is the usual comfort and hygiene target: above the band, condensation and microbial growth; below it, irritation and static discharge.
- Pressure relationships. Ventilation is also used to direct air. Toilets, kitchens and plant rooms are held negative so odours and contaminants stay put; clean spaces and operating theatres are held positive. Getting these wrong undoes good filtration in the adjacent space.
Pressure control is damper control, and a damper that cannot hold position under load breaks the pressure relationship it was installed to maintain. Sizing that actuator correctly is a matter of summing the real torque demand rather than the nominal one; the damper actuator torque calculator does that arithmetic, and the underlying mechanics are covered in damper actuator working principle.
What to specify in a ventilation control package
| Function | Device | Selection note |
|---|---|---|
| Ventilation indicator | Duct CO2 transmitter, NDIR | 0–2,000 ppm; return-air sensing for zone average |
| Comfort measurement | Wall-mount temperature & humidity transmitter | Same electrical standard as the CO2 device |
| Outdoor-air control | Modulating damper actuator | 0–10 V with position feedback; torque sized on the real load |
| Coil control | Motorised ball valve | Match the valve characteristic to the coil |
| Room control and schedule | Fan coil thermostat or controller | Must accept the CO2 signal, or receive it over the bus |
| Signal integrity | Scaling and wiring practice | Document scaling; 4–20 mA for long or noisy runs |
The components are ordinary HVAC parts; what makes a ventilation strategy work is that they are specified as one loop. The system-level view of how they sit together is in air-conditioning system selection for large complex projects, and the signal conventions that tie the loop together are in HVAC control signals. For a quick check of what range a given measurement needs, the sensor range selector and the analog signal calculator both run in the browser with no sign-up.
Summary
Indoor air quality is a measurement and control problem before it is an equipment problem. Ventilation removes what filtration cannot, demand-controlled ventilation makes the fresh-air rate follow the people actually present, and a CO2 measurement is what turns the rate from an assumption into a controlled variable. Get the sensing right, document the scaling, and hold the pressure relationships — then air quality becomes a number on a screen rather than a recurring complaint.